Rack heat & noise calculator

Plan cooling and noise for a server rack, network cabinet or home lab corner: convert the power draw into heat (BTU/h) and the airflow needed to remove it, and add up the noise of several devices at your desk or bedroom door.

Heat

W
°C

Noise

m
m
Heat output
2,730 BTU/h · 0.80 kW
Airflow needed
140 CFM · 239 m³/h
Combined noise
52.1 dB(A) at 1.0 m
At the listener
40.1 dB(A) at 4.0 m

How to use it

  1. Enter the total power draw of everything in the rack — measured at the wall or from the PDU. Practically all of it becomes heat.
  2. Enter how much warmer the exhaust air may be than the intake air (10–15 °C is a common design value).
  3. For noise, enter the dB(A) of each device measured (or specified) at the same distance, then the distance where you sit or sleep.

Formula and method

BTU/h        = watts × 3.412
airflow CFM  ≈ 3.16 × watts ÷ ΔT (°F)        ΔT °F = ΔT °C × 1.8
m³/h         = CFM × 1.699
total dB(A)  = 10 × log10(Σ 10^(Lᵢ ÷ 10))
level at d₂  = L(d₁) − 20 × log10(d₂ ÷ d₁)

Worked example

800 W produce 800 × 3.412 = 2,730 BTU/h. With a 10 °C (18 °F) rise the rack needs 3.16 × 800 ÷ 18 = 140 CFM ≈ 239 m³/h. Two devices at 45 dB(A) and one at 50 dB(A), all measured at 1 m, give 10 × log10(2 × 10^4.5 + 10^5) = 52.1 dB(A); at 4 m that falls by 20 × log10(4) = 12 dB to about 40.1 dB(A).

FAQ

How many BTU/h of air conditioning does my rack need?

At least the rack’s heat output (watts × 3.412) plus the room’s other heat loads such as people, lights and sun, with some margin. A closet without ventilation heats up quickly even with a few hundred watts.

Is 40 dB(A) quiet?

It is roughly the level of a quiet library and usually acceptable in an office; for a bedroom many people want 30 dB(A) or less. Fan noise with tonal whine is more annoying than its dB(A) value suggests.

Why does adding a second identical server only add 3 dB?

Sound energy adds, and decibels are logarithmic: doubling the energy raises the level by 10 × log10(2) ≈ 3 dB.

Related tools

Formulas reviewed November 27, 2026 by Novian · runs entirely in your browser · methodology